About Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -622 - 622 Pa
Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -622 - 622 Pa
APPLICATIONS
DPT-R8 series devices are commonly used in HVAC/R systems for: Fan, blower and filter monitoring Pressure and flow monitoring Valve and damper control Pressure monitoring in clean rooms
WARNING
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.
To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.
Retain these instructions for future reference.
This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by Sensocon. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device.
SPECIFICATIONS
Performance Accuracy (at applied pressure) Ranges < 0.5 inWC = 0.01 inWC Ranges 0.5 inWC = 1.5% inWC Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error
Thermal Effects Temperature compensated across the full spectrum of capability
Overpressure Proof Pressure: 100 inWC Burst Pressure: 120 inWC
Zero Point Calibration Automatic with function or Manual push-button Auto-Zero
Response Time 4.0 0.8 sec, Selectable via Jumper
Technical Specifications Media Compatibility Dry air or non-aggressive gases
Measuring Units (select via Jumper) Pa, kPa, mbar, inWC, mmWC Measuring Element Piezoresistive
Environment: Operating Temperature: 14 122F (-10 50C) Storage Temperature: -4 158F (-20 70C) Humidity: 0 to 95 % rH, non condensing
Physical Case Dimensions: 3.54 x 3.74 x 1.4 (90.0 x 95.0 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 0.1875 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-1 Approved) Protection standard: IP54 / NEMA3
Display (optional) 3 1/2 Digit LCD Backlit Display 2-Line Display (12 character/line) Size: 1.81 W x 0.57 H (46.0 x 14.5 mm)
Electrical connections: 4 screw terminal block Wire: 12-24AWG (0.2 1.5 mm2
Cable Entry Strain Relief: M16 Knockout : 0.625 (16mm)
Pressure Fittings 3/16 (5.2mm) barbed brass + High pressure Low pressure
Electrical Voltage Circuit: 3-wire ([V Out], 24V, GND) Input: 24VAC or VDC, 10% Output: 0-10V or 0-5V, selectable via Jumper Power Consumption: <1.0W Resistance Minimum: 1k
Current Circuit: 3-wire (mA Out, 24V, GND) Input: 24VAC or VDC, 10% Output: 4
Precision Measurement for Demanding EnvironmentsEngineered for both reliability and accuracy, the DPT10-R8 delivers a 1% full scale accuracy for differential pressure readings. Its electronic sensing and configurable output adapt to various industrial needs, from monitoring air filters to managing clean room pressure levels. The rugged design is tailored for wall or surface mounting, making it easy to incorporate into existing control systems.
User-Friendly Display and ConfigurationFeaturing an easy-to-read backlit LCD screen, this transmitter provides clear, real-time pressure readings even in low-light areas. Configuration is straightforward with accessible screw terminals and included mounting screws, while the matte ABS housing ensures long-lasting durability. The DPT10-R8 can be set up for either current or voltage output, suiting different control requirements.
FAQs of Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -622 - 622 Pa:
Q: How is the Sensocon DPT10-R8 Differential Pressure Transmitter installed?
A: The DPT10-R8 can be mounted on any wall or surface using the provided mounting screws. Its screw terminal electrical connections and versatile mounting orientation make installation straightforward for industrial applications.
Q: What types of gases can this transmitter measure?
A: This transmitter is designed to measure the differential pressure of air and other non-corrosive gases, making it ideal for HVAC systems, clean rooms, and other similar environments.
Q: When should I consider using the DPT10-R8 in my application?
A: Use the DPT10-R8 when you require fast, accurate, and reliable pressure measurement, particularly where rapid response time and a configurable output signal are important for process control or monitoring.
Q: Where can this pressure transmitter be used?
A: The DPT10-R8 is suitable for a variety of industrial settings throughout India, including HVAC installations, laboratory environments, filter monitoring, and other situations involving air or non-corrosive gases.
Q: What are the main benefits of the backlit LCD display?
A: The integrated backlit LCD display ensures real-time, easy-to-read pressure measurementsespecially valuable in dimly lit or challenging installation areas, enhancing operational convenience and safety.
Q: How accurate is the DPT10-R8 and what is its scale range?
A: The transmitter offers a scale range from -622 to +622 Pa and provides high precision with an accuracy of 1% of full scale, supporting reliable monitoring in sensitive applications.
Q: What comes included with the Sensocon DPT10-R8 in the box?
A: Each unit ships with mounting screws, an instruction manual, and the pressure transmitter, allowing for a smooth setup and installation process.