Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC
Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC Specification

  • Outer Size
  • 110 mm x 90 mm x 45 mm (Approx.)
  • Seal Material
  • Silicone
  • Thread
  • 1/8 NPT Female
  • Display
  • None (Output signal type device)
  • Sensor Type
  • Differential Pressure Transmitter
  • Grade
  • Industrial
  • Material
  • ABS Plastic Housing
  • Processing Type
  • Electronic
  • Mount Type
  • Wall Mount
  • Scale Range
  • 0 - 5.0 inWC (inches of Water Column)
  • Accuracy
  • 1.0% of FS
  • Finishing
  • Rugged Plastic Enclosure
  • Measure Pressure Of
  • Air and compatible gases
  • Accessories
  • Mounting Screws, Instruction Manual
 

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC Trade Information

  • Payment Terms
  • Cash on Delivery (COD), Cash Against Delivery (CAD), Cash in Advance (CID), Cheque, Cash Advance (CA)
  • Main Export Market(s)
  • Eastern Europe, Middle East, Western Europe, Africa, Central America, South America, Asia, North America, Australia
  • Main Domestic Market
  • All India
 

About Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC

APPLICATIONS 

DPT-R8 series devices are commonly used in HVAC/R systems for: Fan, blower and filter monitoring Pressure and flow monitoring Valve and damper control Pressure monitoring in clean rooms

WARNING 

READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.

Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.

To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.

To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.

Retain these instructions for future reference.

This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by Sensocon. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device. 

SPECIFICATIONS 

Performance Accuracy (at applied pressure) Ranges < 0.5 inWC = 0.01 inWC Ranges 0.5 inWC = 1.5% inWC Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error

Thermal Effects Temperature compensated across the full spectrum of capability 

 Overpressure Proof Pressure: 100 inWC Burst Pressure: 120 inWC

Zero Point Calibration Automatic with function or Manual push-button Auto-Zero

Response Time 4.0 0.8 sec, Selectable via Jumper

Technical Specifications Media Compatibility Dry air or non-aggressive gases

Measuring Units (select via Jumper) Pa, kPa, mbar, inWC, mmWC Measuring Element Piezoresistive

Environment: Operating Temperature: 14 122F (-10 50C) Storage Temperature: -4 158F (-20 70C) Humidity: 0 to 95 % rH, non condensing 

Physical Case Dimensions: 3.54 x 3.74 x 1.4 (90.0 x 95.0 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 0.1875 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-1 Approved) Protection standard: IP54 / NEMA3 

Display (optional) 3 1/2 Digit LCD Backlit Display 2-Line Display (12 character/line) Size: 1.81 W x 0.57 H (46.0 x 14.5 mm) 

Electrical connections: 4 screw terminal block Wire: 12-24AWG (0.2 1.5 mm2 

Cable Entry Strain Relief: M16 Knockout : 0.625 (16mm)

Pressure Fittings 3/16 (5.2mm) barbed brass + High pressure Low pressure 

Electrical Voltage Circuit: 3-wire ([V Out], 24V, GND) Input: 24VAC or VDC, 10% Output: 0-10V or 0-5V, selectable via Jumper Power Consumption: <1.0W Resistance Minimum: 1k

Current Circuit: 3-wire (mA Out, 24V, GND) Input: 24VAC or VDC, 10% Output: 4



Advanced Differential Pressure Sensing

The DPT10-R8 transmitter accurately detects small changes in pressure within an industrial process. Ideal for HVAC systems, cleanrooms, or any application requiring reliable air or gas pressure monitoring, this device offers 1.0% full-scale accuracy. Its electronic processing ensures data stability and minimal drift, essential for process control and safety.


Easy Installation and Setup

Designed for user convenience, the transmitter features screw terminals for quick electrical connections and push-button zero/span adjustments for calibration. Its compact, rugged enclosure includes wall-mount hardware, making integration effortless across diverse setups and orientations.


Durable Operation and Safety

Constructed with an ABS plastic housing and sealed with silicone, the DPT10-R8 provides reliability in environments exposed to dust and light moisture. The IP54 protection class and CE marking underscore its compliance with international safety and quality standards, ensuring dependable, long-term operation in industrial contexts.

FAQs of Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 5.0 inWC:


Q: How do I install the Sensocon Series DPT10-R8 Differential Pressure Transmitter?

A: The DPT10-R8 is designed for wall mounting using the provided screws. Electrical connections are made via screw terminals, and the device can be installed in any orientation. Make sure to reference the instruction manual for specific wiring and mounting guidelines.

Q: What benefits does the 4-20 mA output signal offer for industrial applications?

A: A 4-20 mA output signal provides stable, noise-resistant transmission of measurement data over long distances. It is widely compatible with industrial controllers and monitoring systems, allowing seamless integration and reliable real-time data acquisition.

Q: When is the zero/span adjustment necessary, and how is it performed?

A: Zero/span adjustments are needed during initial setup or periodic maintenance to ensure accurate readings. The DPT10-R8 offers onboard push buttons for convenient calibration without specialized toolssimply press as guided in the manual.

Q: What types of media can be measured with this transmitter?

A: This transmitter is engineered specifically for air and compatible gases. It should not be used with liquids or corrosive gases that may damage the pressure sensor or seals.

Q: Where is the best place to mount the DPT10-R8 for optimal measurement accuracy?

A: While the unit can be installed in any orientation, it is ideal to mount it in a location with stable temperatures and minimal vibration. Ensure the device is not exposed to direct spray or harsh chemicals to maximize lifespan and accuracy.

Q: How does the device handle overpressure situations?

A: The DPT10-R8 is built to tolerate overpressure up to 10 inWC, helping to safeguard the sensor from accidental high-pressure events within its rated limit. Exceeding this could impair sensor performance or damage the device.

Q: What approval or certification does the DPT10-R8 feature?

A: This transmitter is CE marked, which demonstrates conformity with essential European health, safety, and environmental protection requirements, ensuring dependable quality for industrial users.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

More Products in Series DPT Differential Pressure Transmitter India Category

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range  -6.4 - 6.4 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range -6.4 - 6.4 mmWC

Scale Range : 6.4 to +6.4 mmWC

Thread : 1/8 NPT Female

Seal Material : Nitrile Rubber (NBR) or Equivalent

Outer Size : Approximately 85 mm x 85 mm x 58 mm

Mount Type : Other, Wall Mount / Panel Mount

Sensor Type : Differential Pressure Sensor

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range  -12.7 - 12.7 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range -12.7 - 12.7 mmWC

Scale Range : 12.7 to +12.7 mmWC

Thread : 1/8 NPT

Seal Material : Silicone

Outer Size : Compact (Panel Mount Enclosure)

Mount Type : Other, Panel Mount / Wall Mount

Sensor Type : Differential Pressure Sensor

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range  -0.25 - 0.25 mbar

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range -0.25 - 0.25 mbar

Scale Range : 0.25 to 0.25 mbar

Thread : 6 mm hose connection

Seal Material : Silicone

Outer Size : Approx. 90 x 90 x 36 mm

Mount Type : Other, Wall Mount

Sensor Type : Differential Pressure Sensor

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -64 - 64 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -64 - 64 mmWC

Scale Range : 64 to 64 mmWC

Thread : 1/8 NPT Female

Seal Material : Silicone

Outer Size : 124 mm x 84 mm x 55 mm (L x W x D)

Mount Type : Other, Panel or Surface Mount

Sensor Type : Differential Pressure Transmitter



Back to top