Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC
Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC Specification

  • Thread
  • 1/4 NPT Female
  • Grade
  • Industrial
  • Outer Size
  • 110 mm x 110 mm x 56 mm (L x W x D)
  • Seal Material
  • EPDM
  • Display
  • Digital
  • Sensor Type
  • Differential Pressure Transmitter
  • Material
  • ABS Plastic Housing
  • Processing Type
  • Factory Calibrated
  • Diameter
  • 110 mm (face)
  • Mount Type
  • Wall Mount / Surface Mount
  • Scale Range
  • -127 to +127 mmWC
  • Accuracy
  • 0.5% of Full Scale
  • Finishing
  • Powder Coated
  • Measure Pressure Of
  • Air & Non-Corrosive Gases
  • Accessories
  • Mounting Screws, User Manual
 

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC Trade Information

  • Payment Terms
  • Cash on Delivery (COD), Cash Advance (CA), Cash Against Delivery (CAD), Cash in Advance (CID), Cheque
  • Main Export Market(s)
  • Australia, North America, Eastern Europe, Middle East, Africa, Western Europe, Central America, South America, Asia
  • Main Domestic Market
  • All India
 

About Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC 

APPLICATIONS 

DPT-R8 series devices are commonly used in HVAC/R systems for: Fan, blower and filter monitoring Pressure and flow monitoring Valve and damper control Pressure monitoring in clean rooms

WARNING 

READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.

Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.

To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.

To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.

Retain these instructions for future reference.

This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by Sensocon. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device. 

SPECIFICATIONS 

Performance Accuracy (at applied pressure) Ranges < 0.5 inWC = 0.01 inWC Ranges 0.5 inWC = 1.5% inWC Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error

Thermal Effects Temperature compensated across the full spectrum of capability 

 Overpressure Proof Pressure: 100 inWC Burst Pressure: 120 inWC

Zero Point Calibration Automatic with function or Manual push-button Auto-Zero

Response Time 4.0 0.8 sec, Selectable via Jumper

Technical Specifications Media Compatibility Dry air or non-aggressive gases

Measuring Units (select via Jumper) Pa, kPa, mbar, inWC, mmWC Measuring Element Piezoresistive

Environment: Operating Temperature: 14 122F (-10 50C) Storage Temperature: -4 158F (-20 70C) Humidity: 0 to 95 % rH, non condensing 

Physical Case Dimensions: 3.54 x 3.74 x 1.4 (90.0 x 95.0 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 0.1875 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-1 Approved) Protection standard: IP54 / NEMA3 

Display (optional) 3 1/2 Digit LCD Backlit Display 2-Line Display (12 character/line) Size: 1.81 W x 0.57 H (46.0 x 14.5 mm) 

Electrical connections: 4 screw terminal block Wire: 12-24AWG (0.2 1.5 mm2 

Cable Entry Strain Relief: M16 Knockout : 0.625 (16mm)

Pressure Fittings 3/16 (5.2mm) barbed brass + High pressure Low pressure 

Electrical Voltage Circuit: 3-wire ([V Out], 24V, GND) Input: 24VAC or VDC, 10% Output: 0-10V or 0-5V, selectable via Jumper Power Consumption: <1.0W Resistance Minimum: 1k

Current Circuit: 3-wire (mA Out, 24V, GND) Input: 24VAC or VDC, 10% Output: 4


Precision Differential Pressure Sensing

The DPT10-R8 offers high-accuracy differential pressure measurement with a 0.5% full scale accuracy, ensuring dependable results for sensitive HVAC and clean room operations. Its digital display and swift response time under 10 ms make it particularly effective for real-time monitoring and control applications.


Robust Construction & Easy Installation

Encased in a durable, powder-coated ABS plastic housing and rated IP54, this transmitter is built to withstand industrial conditions. It includes mounting screws for fast wall or surface installation, screw terminal electrical connections, and a user-friendly push-button interface for zero and span calibration.


Versatile Applications & Seamless Integration

Suitable for measuring air and non-corrosive gases, the Series DPT10-R8 is commonly used in HVAC, clean rooms, filter monitoring, and building automation environments. Its standard 4-20 mA signal output integrates effortlessly with existing automation systems, providing flexibility and reliability.

FAQs of Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range -127 - 127 mmWC:


Q: How is the Sensocon DPT10-R8 differential pressure transmitter installed?

A: The device is designed for easy wall or surface mounting using the included screws. Electrical connections are made via screw terminals, and it connects via 1/4 NPT female threads to compatible piping.

Q: What types of gases can this transmitter measure?

A: The DPT10-R8 is designed to measure the differential pressure of air and other non-corrosive gases, making it ideal for HVAC and clean room environments.

Q: When should the zero and span adjustment be performed?

A: Zero and span adjustments should be carried out during initial setup or when recalibration is required, using the push-buttons located on the front panel for hassle-free configuration.

Q: Where can the DPT10-R8 transmitter be used?

A: This unit is suitable for use in various industrial and commercial settings, including HVAC systems, clean room monitoring, filter status tracking, and building automation in environments across India.

Q: What is the process for connecting the DPT10-R8 to a monitoring system?

A: Simply connect the transmitters 4-20 mA (2-wire) output to your building management or automation system, ensuring a 10-30 VDC power supply and secure screw terminal connections.

Q: How does the device benefit HVAC and clean room applications?

A: With its high accuracy, fast response time, and durable design, the DPT10-R8 provides real-time, reliable pressure readings critical for ensuring proper ventilation, air quality, and system efficiency in sensitive environments.

Q: What accessories come with the DPT10-R8 transmitter?

A: Each unit is supplied with mounting screws and a user manual to streamline installation and provide clear operational guidance.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

More Products in Series DPT Differential Pressure Transmitter India Category

Sensocon USA Differential Pressure Transmitter Series DPT30-R8 - Range  0 - 75 mbar

Sensocon USA Differential Pressure Transmitter Series DPT30-R8 - Range 0 - 75 mbar

Sensor Type : Differential Pressure Transmitter

Processing Type : Other, Electronic

Material : Other, ABS Plastic Housing

Mount Type : Other, Wall Mount

Scale Range : 0 75 mbar

Accessories : Mounting Screws, Instruction Manual

Sensocon USA Series DPT1-R8 - Range 0 - 0.5 in WC

Sensocon USA Series DPT1-R8 - Range 0 - 0.5 in WC

Sensor Type : Differential Pressure Sensor

Processing Type : Other, Electronic

Material : Other, Polycarbonate Enclosure

Mount Type : Other, Wall Mount

Scale Range : 0 0.5 in WC

Accessories : Mounting Kit, User Manual

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range  -2.5 - 2.5 mmWC

Sensocon USA Differential Pressure Transmitter Series DPT1-R8 - Range -2.5 - 2.5 mmWC

Sensor Type : Differential Pressure Transmitter

Processing Type : Other, Electronic Measurement

Material : Other, ABS Housing

Mount Type : Other, Panel Mount

Scale Range : 2.5 to 2.5 mmWC

Accessories : Mounting Screws, User Manual

Series DPT Range Differential Pressure Transmitter

Series DPT Range Differential Pressure Transmitter

Sensor Type : Differential Pressure Sensor

Processing Type : Other, Electronic

Material : Other, ABS Plastic Housing

Mount Type : Other, Wall or Panel Mount

Scale Range : 0 to 250 Pa, 0 to 400 Pa, 0 to 1000 Pa (Modeldependent)

Accessories : Mounting Screws, Instruction Manual



Back to top