About HUBA Control Differential Pressure Transmitter 692.911017011

HUBA Control Differential Pressure Transmitter 692.911017011
- Brand : Huba Control
- Model : 692.911017011
- Range : 0...+1 BAR
- Type : 692 0...+1 BAR
- Current Out : 4-20mA
- Voltage : 11-33V DC
- MAX : P1-P2 2BAR
- MAX : P2-P1 2BAR
- Made In Switzerland
Huba Control Differential Pressure Transmitter
Product Information
Differential Pressure Transmitter 692
The Pressure Transmitters of Type 692 Feature The Unique And Proven Ceramic Technology. Depending On The Application, Various Pressure Connections And Electrical Connections With Standardized Output Signals Are Available. Due To The Wide Variety Of Options, The Transmitters 692 Are Suitable For All Types Of Industrial Applications.
- Very Low Temperature Sensitivity
- High Temperature Resistance
- No Mechanical Creep
- Individual Applications Through Modular System And Different Material Choices
Technical Data
Product Feature
- Pressure Measuring Range : 0 ... 25 Bar (Relative And Difference)
- Response Time : <5 ms
- Load Change : <50 Hz
- Sensor Weight : 430 g
Field Of Application
- Media : Process Medium; Gas
- Medium Temperature : -15 ... 85 C
- Permissible Overload On One Side : See Variant Plan
- System Pressure : 12; 25; 50 Bar
- Bursting Pressure : 1.5 x System Pressure
Ambient Condition
- Ambient Temperature : -15 ... 85 C
- Storage Temperature : -40 ... 85 C
Material
- Housing : Stainless Steel 1.4305 (AISI 303); PVDF
- Pressure Connection With Media Contact : Stainless Steel 1.4305 (AISI 303); PVDF; CuZn Vni
- Measuring Element With Media Contact : Ceramic Al2O3 (96 %)
- Sealing Material With Media Contact : FPM; EDPM; NBR; MVQ; CR
Electrical Data
- Current Consumption : <20 mA
- Inverse-Polarity Protection : Short-Circuit And Reverse Polarity Protected. Each Connection Against Each Other With Max. Supply Voltage.
Installation Guide
- Installation Orientation : any
- Assembly : Mounting Bracket
Approval
EMC Compatibility : CE-Compliant In Accordance With EN 61326-2-3
Applications
- REFRIGERATION SYSTEMS
- CPU
- WATER PUMPS
- ULTRAFILTRATION SYSTEM
Accessories
- Mounting Bracket
- Socket Outlet DIN EN 175301-803-A : With Seal; IP 65, When Mounted And Screwed.
- Socket Outlet DIN EN 60130-9 : IP 65, When Mounted And Screwed.
- Calibration Certificate
Additional Information:

Precision in Differential Pressure MeasurementDesigned for accuracy and stability, the HUBA Control Differential Pressure Transmitter 692.911017011 supports a wide voltage range (11-33 VDC) and delivers dependable performance for gas and process medium monitoring. Its stainless steel and PVDF construction guarantee robust operation and resistance to harsh industrial conditions.
Versatile Output and Easy IntegrationSupporting output signals of 0-5 V, 0-10 V, and 4-20 mA, this transmitter adapts easily to various control and monitoring systems. Its compact size and standard thread size (6 mm) facilitate straightforward installation in limited spaces, making it suitable for both system upgrades and new projects.
FAQ's of HUBA Control Differential Pressure Transmitter 692.911017011:
Q: How does the HUBA Control Differential Pressure Transmitter 692.911017011 function in a process medium application?
A: This transmitter measures the pressure difference between two points in process gas applications, converting the pressure reading into a standardized electrical output (0-5 V, 0-10 V, or 4-20 mA) for process control or data monitoring systems.
Q: What are the main benefits of selecting the 692.911017011 model for industrial use?
A: The main benefits include high accuracy in low differential pressure ranges (0...+1 BAR), robust construction with stainless steel and PVDF for enhanced durability, multiple output options, and compatibility with a wide input voltage (11-33 VDC), ensuring flexibility for various industrial settings.
Q: When should I use this transmitter in my system?
A: It is ideal to use this transmitter whenever precise monitoring of gas pressure differences in industrial processes is required, particularly where robust build quality and multiple signal outputs are essential for integration with process controllers or safety systems.
Q: Where can I install the HUBA Control Differential Pressure Transmitter, and what is the recommended mounting process?
A: The device can be installed in any suitable position within your process line, thanks to its compact dimensions. Ensure proper connection to process pipes or tanks using its 6 mm thread and follow manufacturer guidelines for wiring the 11-33 VDC supply and output signals.
Q: What applications are best suited for the HUBA Control Differential Pressure Transmitter 692.911017011?
A: It is particularly suited for industrial gas processing, HVAC systems, filter monitoring, and any scenario where precise and dependable differential pressure measurements are crucial. Its versatility makes it popular among exporters, distributors, and process industries in India.
Q: How do the different output signals benefit process integration?
A: The selectable outputs (0-5 V, 0-10 V, and 4-20 mA) permit seamless connectivity with a range of controllers, PLCs, and monitoring devices, allowing customization for either analog or digital system requirements and promoting straightforward integration into existing plants.