About Sensocon USA 212-D020I-3 Differential Pressure Transmitter
Sensocon USA 212-D020I-3 Differential Pressure Transmitter
- Maximum Pressure: Ranges : 5 PSI (35 kPa) = 15 PSI (100kPa) Max Ranges > 5 PSI (35 kPa) = 30 PSI (200kPa) Max
- Media compatibility: Air and compatible non-combustible, non-corrosive gases
- Accuracy: Ranges : 4" w.c. (1kPa) 1.0% Ranges : 5" w.c. (1.25kPa) 0.25%
- Temperature Ranges: Compensated: 15° to 120°F (-10° to 50°C)Operating: -10° to 155°F (-25° to 70°C)
- Thermal Effect: +/- 0.028% FS/°F (+/- 0.50% FS/C)
- Stability: +/- 0.25% FS/year
- Output Signal: 4-20 mA, 2-wire or 0 - 10 V
- Loop Resistance: 250-24 VDC
- Power Supply: 12-30 VDC
- Enclosure Rating: IP 65
- Electrical Connections: screw terminals
- Electrical Entry: PG7 Cable Gland
- Process Connection: Barbed fittings for 3/16 flexible tubing
- Agency Approvals: CE
Key Features for Industrial ApplicationsThe Sensocon 212-D020I-3 is tailored for industrial-grade differential pressure monitoring, ideal for HVAC, clean rooms, or filtration systems. It operates reliably within 0 to 50C, thanks to its IP65-rated enclosure and robust polycarbonate build. Its fast response time under 100 ms and high-accuracy sensor ensure consistent, real-time monitoring, which is essential for process control and safety.
User-Friendly Adjustments and DisplayAdjusting and reading measurements is straightforward with the transmitters push-button zero/span on its front panel and a clear, 4-digit digital LCD. The accessible interface means minimal downtime or training, letting operators perform calibrations or troubleshooting quickly without dismantling the setup.
Dependable Installation and VersatilityWith a compact, rectangular form (122 x 70 x 43 mm) and wall/surface mount configuration, the transmitter fits diverse installation scenarios. Its 1/8 NPT female process connections, 3-pin terminal block, and wide 1236 VDC power range accommodate various industrial setups, making it a dependable solution for suppliers, traders, and end-users alike.
FAQs of Sensocon USA 212-D020I-3 Differential Pressure Transmitter:
Q: How do I adjust the zero and span settings on the Sensocon 212-D020I-3?
A: Zero and span adjustments are easily made using the push-buttons on the front panel, allowing for convenient calibration without opening the enclosure or removing the device from its mount.
Q: What is the main benefit of the 212-D020I-3s polycarbonate enclosure?
A: The high impact polycarbonate enclosure offers IP65 (NEMA 4X) protection, safeguarding the transmitter against dust, moisture, and physical impacts, which is ideal for harsh industrial settings.
Q: When should this differential pressure transmitter be used?
A: The Sensocon 212-D020I-3 is best suited for monitoring air and non-corrosive gases in environments such as HVAC systems, clean rooms, or process control applications where quick, accurate pressure measurement is required.
Q: Where can the transmitter be installed?
A: This device is designed for wall or surface mounting in indoor locations, thanks to its compact size and rectangular casing, making it adaptable to a variety of industrial or commercial setups.
Q: What electrical connection does the device use?
A: The 212-D020I-3 uses a 3-pin terminal block for electrical connections and outputs a standard 420 mA (two-wire) signal, ensuring straightforward wiring and integration with control systems.
Q: How accurate is the Sensocon 212-D020I-3 and what pressure range does it measure?
A: It delivers high measurement accuracy within 1.0% FS and covers a differential pressure range of 0 to 20.0 inches of water column (in. H2O), making it reliable for precision applications.
Q: What accessories are provided with the product?
A: The package includes mounting screws, an instruction manual, and a calibration certificate to facilitate seamless installation and compliance with quality standards.