Series 211 Differential Pressure Transmitter
The Series 211 Differential Pressure Transmitter can accurately measure positive, negative, or differential pressure and send the corresponding 4-20 mA output signal. The Series 211 Differential Pressure Transmitter is not position sensitive and can be mounted in any orientation without compromising accuracy. It also features a power LED, so you always know when the transmitter is operating. The compact, lightweight design makes installation simple and easy.
| Model | Pressure Range | Accuracy |
| 211-D001I-1 | 0-1 | 1% |
| 211-D002I-1 | 0-2 | 1% |
| 211-D004I-1 | 0-4 | 1% |
| 211-D006I-3 | 0-6 | 0.25% |
| 211-D010I-3 | 0-10 | 0.25% |
| 211-D020I-3 | 0-20 | 0.25% |
| 211-D040I-3 | 0-40 | 0.25% |
| 211-D005P-3 | 0-5 PSI | 0.25% |
| 211-D010P-3 | 0-10 PSI | 0.25% |
| 211-D015P-3 | 0-15 PSI | 0.25% |
| 211-D250A-1 | 0-250 Pa | 1% |
| 211-D500A-1 | 0-500 Pa | 1% |
| 211-D001K-1 | 0-1 kPa | 1% |
| 211-D002K-3 | 0-2 kPa | 0.25% |
| 211-D003K-3 | 0-3 kPa | 0.25% |
| 211-D005K-3 | 0-5 kPa | 0.25% |
| 211-D010K-3 | 0-10 kPa | 0.25% |
| 211-D025K-3 | 0-25 kPa | 0.25% |
| 211-D050K-3 | 0-50 kPa | 0.25% |
| 211-D100K-3 | 0-100 kPa | 0.25% |
For 0-10 V output, add -V to the end of the part number. Consult factory for other calibration ranges including zero center ranges.
Reliable Industrial-Grade Pressure MeasurementThe Series 211 Differential Pressure Transmitter is engineered for rigorous industrial environments, thanks to its solid-state electronics and an enclosure rated NEMA 4X (IP66). Its robust ABS construction and silicone seal ensure durability and protection against dust and water. The transmitter is ideally suited for monitoring air flows and pressures in HVAC, filter monitoring, and other process control tasks, delivering both longevity and consistent accuracy.
Flexible Outputs and Easy IntegrationOffering field-selectable output signals (4-20 mA or 0-10 VDC) and supporting both 2-wire and 3-wire configurations with a 12-36 VDC power supply, this transmitter integrates seamlessly into a wide range of systems. Installation is straightforward with screw terminal blocks for electrical connections and barbed fittings for pressure hoses. The included standard mounting kit supports quick surface or wall mounting, optimizing setup time.
Precision and User-Friendly OperationDesigned for hassle-free operation, the Series 211 features digital display and push-button zero/span adjustment, allowing precise calibration directly at the installation site. With fast response time (<100 ms) and high accuracy (1% FS), users can rely on real-time, dependable data for critical applications. Various pressure scale ranges and simple maintenance make it a valuable tool for professionals.
FAQs of SENSOCON Mack USA Series 211 Differential Pressure Transmitter WHOLESALER:
Q: How can I switch between 4-20 mA and 0-10 VDC output signals on the Series 211 transmitter?
A: You can select either 4-20 mA or 0-10 VDC output by adjusting the field-selectable jumper settings inside the transmitter. Make sure to power off the device before accessing and updating these settings according to your systems requirements.
Q: What types of applications are best suited for the Series 211 Differential Pressure Transmitter?
A: The Series 211 is ideal for HVAC systems, filter monitoring, cleanroom pressure control, and process automation, thanks to its accuracy, quick response, and ability to measure air and compatible gases. Its robust design is perfect for demanding industrial environments.
Q: Where should I mount the Series 211 for optimal performance?
A: This transmitter can be mounted on a wall or any flat surface using the provided mounting kit. Ensure it is placed in a location protected from direct sunlight and excessive vibration for the most stable and accurate readings.
Q: What is the procedure for zero and span adjustment on this device?
A: Zero and span adjustments are made easily via the front push-button controls. For precise calibration, follow the instructions in the product manual to zero the transmitter and set the full-scale span after installation.
Q: How does the NEMA 4X (IP66) enclosure benefit industrial installations?
A: The NEMA 4X (IP66) enclosure provides excellent resistance to water, dust, and corrosion. This ensures reliable operation in harsh industrial environments, reducing maintenance needs and enhancing service life.
Q: What electrical connections are required for the Series 211 pressure transmitter?
A: The transmitter uses screw terminal blocks for straightforward connection to either 2-wire or 3-wire circuits, powered by a 12-36 VDC supply. Refer to the wiring diagram supplied with the unit to ensure proper installation.
Q: When should I consider recalibrating or checking the transmitter for accuracy?
A: Periodic recalibration is recommended, especially in critical applications. Follow your facilitys calibration schedule, or recalibrate any time the transmitter is exposed to mechanical shock or after extended periods of use, ensuring ongoing accuracy.