About Dwyer DM-007 DigiMag Differential Pressure Transmitter Range 0-3 Inch WC

Dwyer DM-007 DigiMag Differential Pressure Transmitter Range 0-3 Inch WC
Senses The Pressure of Air and Compatible Gases, This Differential Pressure Transmitter Features a Pressure Range of 3 inWC and Has a 4 to 20 mA output. Fast and Easy to Set up, This Transmitter is Suitable for Fan Control, Static Pressures in ducts or buildings, room Pressurization Monitoring, and Differential Pressure Across Filters.
Dwyer DM-007 Offers
Specifically Designed to Mount in a standard Magnehelic Gauge cutout, this pressure transmitter features a polycarbonate molded housing with integral pressure connections, reducing installation time. In addition, the digital push-button zero and span simplify calibration over typical turn-potentiometers, and a single push-button allows field selection of multiple engineering units.
Features
- Reduced installation time through zero and span controls that provides quick and easy calibration
- Fast and easy setup and calibration with push-button zero and span controls
- Immediate corrective action can be taken by local alerts via the easy-to-read LCD display
- Reduces upgrade installation costs and simplifies field upgrade from a Magnehelic Gauge, as both use the same diameter cutout
Applications
- Differential Pressure Across Filters
- Fan Control
- Static Pressures in Ducts or Buildings
- Room Pressurization Monitoring
Dwyer DM-007 Specifications
| Service |
Air And Non-Combustible, Compatible Gases |
| Pressure Range |
3 inWC |
| Accuracy |
1% FSO |
| Stability |
<1%/year FSO |
| Limits |
Pressure: 3.6 psi maximum operation, 6 psi burst Temperature: -4 to 158F (-20 to 70C) |
| Thermal Effect |
0.02% FS/F (0.036% FS/C) |
| Output Signal |
4 to 20 mA (2-wire) |
| Zero and Span Adjustments |
Push-button |
| Loop Resistance |
0 to 1250 I maximum |
| Current Consumption |
21 mA maximum |
| Connections |
Electrical: Screw-type terminals Process: Male ports on side for ", 316", 14", 0.2" (5 mm), 0.23" (6 mm) ID flexible tubing |
| Power Requirements |
10 to 35 V DC (2-wire) |
| Enclosure Rating |
NEMA 4X (IP66) |
| Mounting Orientation |
Not sensitive to position |
| Agency Approvals |
CE |
| Housing Material |
Polycarbonate |
| Dimensions |
5 x 1.9" (127 x 48.2 mm) |
| Weight |
7.04 oz (200 g) |
Click Here For Complete Specifications On The
Dwyer DM-007What's included with the Dwyer DM-007
- Dwyer DM-007 DigiMag Differential Pressure Transmitter, 3 inWC
Additional Information:
- Item Code: DM-007-DigiMag-DP-Transmitter-Range-0-3-Inch-WC
- www.envirotechindustrialproduct.com
- www.envirotechindustrialproducts.com
- www.envirotechdelhi.com

Accurate Digital Pressure Monitoring
The Dwyer DM-007 DigiMag Differential Pressure Transmitter ensures high-precision gas pressure measurements across various industrial processes. Its digital YAS display provides clear readings, helping operators monitor and control pressure with confidence. Customizable scale options and a clearly marked 4-inch dial enhance usability, making this device suitable across a range of pressure measurement applications.
Versatile Industrial Applications
Designed for demanding environments, the DM-007 transmitter is perfect for use in power plants, cement factories, steel manufacturing, fertilizer production, and textile industries. Its adaptable measurement range and durable plastic construction make it a top choice for Indian distributors, suppliers, and engineers seeking a reliable pressure transmitter.
FAQ's of Dwyer DM-007 DigiMag Differential Pressure Transmitter Range 0-3 Inch WC:
Q: How does the Dwyer DM-007 DigiMag Differential Pressure Transmitter measure pressure?
A: The DM-007 uses a sensitive differential system to detect and digitally display the pressure difference between two points, specifically for gas applications within the range of 0-3 Inch WC. Multiple scale options, including MM WC, CM, PAC, KPA, and INCH, enable flexible unit readings.
Q: What types of industries can benefit from using the DM-007 DigiMag transmitter?
A: Industries such as power generation, cement manufacturing, steel plants, fertilizer production, and textile processing can all benefit from the DM-007's accurate and reliable gas pressure monitoring capabilities.
Q: When should the DM-007 differential pressure transmitter be calibrated?
A: Calibration should typically be performed during initial installation, after any major process changes, or as part of standard periodic maintenance to ensure ongoing accuracy within 1% FSO.
Q: Where can the DM-007 transmitter be installed within an industrial facility?
A: The DM-007 can be installed wherever differential gas pressure measurement is required, such as pipelines, HVAC ducts, process chambers, or filtration systems, depending on the specific industrial process.
Q: What is the process for commissioning the DM-007 in a new application?
A: To commission the DM-007, mount the device securely, connect it to the pressure sources, select the appropriate measurement scale on the digital display, and verify its accuracy through a calibration check before full-scale operation.
Q: How does the plastic construction of the DM-007's dial and pointer benefit users?
A: The plastic dial and pointer offer durability, resistance to corrosion, and a lightweight design, reducing maintenance needs and ensuring accurate readings even in challenging industrial environments.
Q: What are the primary benefits of using the DM-007 DigiMag Differential Pressure Transmitter?
A: Key benefits include high measurement accuracy, versatile multi-scale readings, easy installation, lightweight build, and adaptability for various industrial uses, making pressure monitoring efficient and reliable.