Sensocon USA Differential Pressure Transmitter Series DPT30-R8 - Range 0 - 50 mbar
APPLICATIONS
DPT-R8 series devices are commonly used in HVAC/R systems for: Fan, blower and filter monitoring Pressure and flow monitoring Valve and damper control Pressure monitoring in clean rooms
WARNING
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.
To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.
Retain these instructions for future reference.
This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by Sensocon. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device.
SPECIFICATIONS
Performance Accuracy (at applied pressure) Ranges < 0.5 inWC = 0.01 inWC Ranges 0.5 inWC = 1.5% inWC Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error
Thermal Effects Temperature compensated across the full spectrum of capability
Overpressure Proof Pressure: 100 inWC Burst Pressure: 120 inWC
Zero Point Calibration Automatic with function or Manual push-button Auto-Zero
Response Time 4.0 0.8 sec, Selectable via Jumper
Technical Specifications Media Compatibility Dry air or non-aggressive gases
Measuring Units (select via Jumper) Pa, kPa, mbar, inWC, mmWC Measuring Element Piezoresistive
Environment: Operating Temperature: 14 122F (-10 50C) Storage Temperature: -4 158F (-20 70C) Humidity: 0 to 95 % rH, non condensing
Physical Case Dimensions: 3.54 x 3.74 x 1.4 (90.0 x 95.0 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 0.1875 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-1 Approved) Protection standard: IP54 / NEMA3
Display (optional) 3 1/2 Digit LCD Backlit Display 2-Line Display (12 character/line) Size: 1.81 W x 0.57 H (46.0 x 14.5 mm)
Electrical connections: 4 screw terminal block Wire: 12-24AWG (0.2 1.5 mm2
Cable Entry Strain Relief: M16 Knockout : 0.625 (16mm)
Pressure Fittings 3/16 (5.2mm) barbed brass + High pressure Low pressure
Electrical Voltage Circuit: 3-wire ([V Out], 24V, GND) Input: 24VAC or VDC, 10% Output: 0-10V or 0-5V, selectable via Jumper Power Consumption: <1.0W Resistance Minimum: 1k
Current Circuit: 3-wire (mA Out, 24V, GND) Input: 24VAC or VDC, 10% Output: 4
The DPT30-R8 Series Transmitter provides consistent and accurate differential pressure measurement for critical processes such as HVAC systems, cleanroom monitoring, and air handling units. Its advanced electronic processing ensures rapid response times and reliable output, supporting stringent industrial requirements.
Designed with user convenience in mind, the DPT30-R8 features a compact, wall-mountable housing and barbed pressure ports for straightforward connection. Screw terminals make electrical installation secure and easy, while supplied mounting screws enable hassle-free setup in a variety of locations.
FAQs of Sensocon USA Differential Pressure Transmitter Series DPT30-R8 - Range 0 - 50 mbar:
Q: How is the Sensocon DPT30-R8 Differential Pressure Transmitter typically installed?
A: The DPT30-R8 is designed for simple wall mounting using the included mounting screws. Its compact housing allows it to fit easily into tight spaces, making it ideal for HVAC, cleanrooms, and air handling system installations.
Q: What type of output signal does the DPT30-R8 transmitter provide?
A: This transmitter delivers a standard 4-20 mA output signal, which is widely compatible with industrial control systems for monitoring and automation purposes.
Q: When should this transmitter be used within a system?
A: The DPT30-R8 is best employed when precise, real-time monitoring of differential air or non-aggressive gas pressure is required, such as in cleanroom environments or to track filter and airflow performance in HVAC systems.
Q: Where can the DPT30-R8 be deployed for optimal benefit?
A: It is ideal for use in any application where differential pressure monitoring of air or non-aggressive gases is essential, including industrial HVAC units, cleanrooms, air handling units, and ventilation systems across commercial and industrial sites.
Q: What is the process for connecting the electrical terminals?
A: Electrical connections are made using screw terminals, which ensure a secure attachment for wiring. The device operates on a 24 VDC power supply, with a voltage acceptance range of 12-36 VDC for flexibility during installation.
Q: What are the benefits of using this differential pressure transmitter?
A: The DPT30-R8 offers high measurement accuracy (1% F.S.), rapid response time (<10 ms), and robust performance in challenging environments. Its industrial-grade construction and adaptable power input provide reliability and peace of mind for continuous operations.